Various raw waters contain a certain concentration of suspended solids and dissolved substances. Suspended solids are mainly inorganic salts, colloids and biological particles such as microorganisms and algae. The soluble substances are mainly soluble salts and insoluble salts (such as carbonates, sulfates and silicates), metal oxides, acids and bases. During reverse osmosis, the volume of influent water is decreasing and the concentration of suspended particles and dissolved substances is increasing. Suspended particles can deposit on the membrane, blocking the inlet flow path and increasing frictional resistance (pressure drop). When the insoluble salt exceeds its saturation limit, it will precipitate from the concentrated water, form scaling on the membrane surface, reduce the flux of the RO membrane, increase the operating pressure and pressure drop, and lead to a decrease in the product water quality. This phenomenon of forming a deposited layer on the membrane surface is called membrane fouling, and the result of membrane fouling is the deterioration of system performance. It is necessary to perform pretreatment before the raw water enters the reverse osmosis membrane system to remove suspended solids, dissolved organics and excess insoluble salt components that may pollute the reverse osmosis membrane, and reduce the tendency of membrane fouling. The purpose of pretreatment of the influent is to improve the quality of the influent, so that the RO membrane can obtain a reliable operation guarantee.
1. Daily operation inspection of water treatment equipment pretreatment
1. After entering normal production, the operator should regularly inspect the equipment site every hour. Record the inspection results truthfully and summarize them together with the operation records as data for regular maintenance.
2. Inspection cycle - inspection items - inspection methods or inspection points - remarks;
3. Once per shift - check whether there is water leakage - whether there is water leakage in the sealing parts and auxiliary valves of the equipment - if there is water leakage - find out the location and cause of the leakage point, and stop the leakage in time;
4. Check whether there is vibration - when the valve is opened and closed, whether there is abnormal vibration - if there is vibration, find out the cause and take timely measures;
5. Once a month - check flow rate - check the flow meter indication value to verify whether it indicates normal flow rate - if the flow rate display is abnormal, find out the reason in time and eliminate the fault.
2. Regular inspection of pretreatment of water treatment equipment
The equipment is subject to regular inspections, the purpose of which is to ensure the safe operation of the system over a longer period of time. This equipment is relatively large, and inspection work takes a long time. In order to shorten the downtime of regular inspection, it should be carried out at the same time as possible with the maintenance of other equipment and devices of the raw water treatment plant. If any abnormality is found, it should be dealt with in time.
1. Packing inspection - check the activated carbon filter material, if the activated carbon filter material loses its adsorption effect, it should be replaced.
2. Check the water filter cap - take out the packing, rinse it with water, check the water filter cap on the porous plate, if it is found damaged or loose, replace or fix it in time.
3. Inspection of the rubber lining layer - if it is found that the rubber lining has bubbles, cracks, glue peeling, micro holes, etc., it should be repaired.
4. Internal fastener inspection - check the bolts and nuts and other fasteners in the filter, if they are loose, they should be tightened.
5. Inspection of manhole gaskets—replace the deformed manhole gaskets; immerse the bolts and nuts in cleaning oil to remove rust thoroughly; apply butter to the bolts and nuts when installing the manhole cover.
3. Water treatment equipment pretreatment filter material replacement
1. Drainage - Drain the accumulated water inside the filter;
2. Discharge - open the discharge port of the filter, enter a small amount of water from the backwash port, and flush the filler out.
3. Cleaning - Drain the accumulated water in the filter, open the manhole, enter the filter, and clean the remaining filter material out of the filter;
4. Cleaning - clean the inside of the filter with a rag;
5. Filling the filter material - close the discharge port, fill the filter material according to the regulations, first load the quartz sand, and then flatten it, and then load the activated carbon;
6. Close the filter - check that the filling height of the filter material meets the requirements, and close the upper manhole;
7. Rinse the filter material - rinse the filter material according to the filter backwashing steps until the turbidity of the drainage is less than 1 degree.
Daily inspection and maintenance of water treatment equipment pretreatment